Testing emergency generators thoroughly is of great importance as regular testing ensures that they are in excellent working order. It offers a number of benefits and assists facility executives. One prime objective of load bank testing is to maintain accurate records of how and when generators were evaluated. Most importantly, load bank testing makes sure that emergency power generators are ready to take over when main electricity supply interrupts.
Power System Plus provides rental solutions for your power needs, whether you have to perform maintenance and commissioning or looking for a portable load for evaluation purposes. Our rental load bank service makes sure that your power generators support loads by maintaining frequencies and voltages that are compatible with design criteria.
Our rental load banks in Edmonton, ranging from 150 KW to 1500 KW, will provide you the best and affordable load testing solutions. Stay ready to counter power failures. Feel Free to discuss your projects and power systems testing needs with us.
RENTAL UNIT # P278, A382 & S459
Approx. Weight: 200lbs
Approx. Dimesions: 45” H x 23” W x 29” D
VOLTS | STEP 1 | STEP 2 | STEP 3 | STEP 4 | STEP 5 | TOTAL |
---|---|---|---|---|---|---|
240 VOLT |
1 | 3 | 5 | 10 | 18 | 37KW |
208 VOLT |
2 | 4 | 7 | 14 | 28 | 55KW |
480 VOLT |
3 | 6 | 13 | 26 | 49 | 97KW |
600 VOLT |
5 | 10 | 20 | 40 | 75 | 150KW |
RENTAL UNIT #’S 134, A240 P264-1, P270
Approx. Weight: 230lbs
Approx. Dimesions: 53” H x 26” W x 30” D
VOLTS | STEP 1 | STEP 2 | STEP 3 | STEP 4 | STEP 5 | STEP 6 | TOTAL |
---|---|---|---|---|---|---|---|
240 VOLT |
1 | 3 | 5 | 10 | 18 | 25 | 62KW |
208 VOLT |
2 | 4 | 7 | 14 | 28 | 37 | 92KW |
480 VOLT |
3 | 6 | 13 | 26 | 48 | 64 | 160KW |
600 VOLT |
5 | 10 | 20 | 40 | 75 | 100 | 250KW |
RENTAL UNIT #’S P265-2, P317 & P335
Approx. Weight: 375lbs
Approx. Dimesions: 64” H x 32” W x 37” D
VOLTS | STEP 1 | STEP 2 | STEP 3 | STEP 4 | STEP 5 | STEP 6 | STEP 7 | TOTAL |
---|---|---|---|---|---|---|---|---|
240 VOLT |
1 | 2 | 4 | 6 | 12 | 25 | 50 | 100KW |
208 VOLT |
1.5 | 2.5 | 5 | 9 | 18 | 37 | 74 | 147KW |
480 VOLT |
2.5 | 4.5 | 9 | 16 | 32 | 64 | 128 | 256KW |
600 VOLT |
4 | 7 | 14 | 25 | 50 | 100 | 200 | 400KW |
RENTAL UNIT #’S P360 & R546
Approx. Weight: 390lbs
Approx. Dimesions: 64” H x 32” W x 37” D on casters
VOLTS | STEP 1 | STEP 2 | STEP 3 | STEP 4 | STEP 5 | STEP 6 | STEP 7 | TOTAL |
---|---|---|---|---|---|---|---|---|
480 VOLT |
16 | 32 | 64 | 64 | 64 | 80 | 80 | 400KW |
600 VOLT |
25 | 50 | 100 | 100 | 100 | 125 | – | 500KW |
RENTAL UNIT #’R527 & #S370
Approx. Weight: 1750lbs Load Bank – Trailer weight 2050lbs
Approx. Dimesions on trailer: (87′ H x 244” L x 103” W) – (Without Trailer) 64” H x 115” W x 60” D
VOLTS | STEP 1 | STEP 2 | STEP 3 | STEP 4 | STEP 5 | STEP 6 | STEP 7 | TOTAL |
---|---|---|---|---|---|---|---|---|
480 VOLT |
16 | 32 | 64 | 128 | 192 | 256 | 272 | 960KW |
600 VOLT |
25 | 50 | 100 | 200 | 300 | 400 | 425 | 1500KW |